Product Overview
The MW5 series intelligent universal circuit breaker (hereinafter referred to as circuit breaker) is suitable for AC 50/60Hz, with a rated voltage of 400V, 690/800V, 1140V, and a rated current of 200~7500A. It is mainly used in the distribution network to distribute power and protect lines and power equipment from overload, undervoltage, short circuit, single-phase grounding faults. The circuit breaker has a variety of intelligent protection functions, which can achieve selective protection and precise operation. Its technology can reach the advanced level of similar international products, and is equipped with a communication interface, which can perform "four remotes" to meet the requirements of the control center and automation system. Avoid unnecessary power outages and improve power supply reliability.
This series of products complies with IEC60947-2, GB/T14048.2 standards.
Model meaning
Codename | project | Codename | project |
① | Company code: Shanghai Muller | ④ | Frame grade rated current: 1600A, 2500A, 4000A, 7500A |
② | Universal circuit breaker | ⑤ | Controller model: See Protection Function Table |
③ | Design code | ⑥ | Number of poles: 3P, 4P |
Main technical parameters
model | MW5-1600 | MW5-2000/2500 | MW5-4000 | MW5-7500 | |
Rated operating current In(A) | 200,315,400, 500,630, 800,1000, 1250,1600 | 400,630,800, 1000,1250,1600, 2000,2500 | 2000,2500, 2900,3200, 3600,3900, 4000 | 5000,6300, 7500 | |
Pole number | 3P/4P | 3P/4P | 3P/4P | 3P/4P | |
Rated limit short circuit breaking capability Icu(kA) | 400V | 50 | 85 | 120 | 140 |
690V/800V | 35 | 50 | 65 | 80 | |
1140V | 20 | 30 | 50 | 55 | |
Rated short circuit breaking capability Ics(kA) | 400V | 50 | 65 | 100 | 140 |
690V/800V | 35 | 50 | 65 | 80 | |
1140V | 20 | 30 | 50 | 55 | |
Rated short circuit switch-on capability Icm(kA)(peak)/cosΦ | 400V | 105 | 187 | 264 | 308 |
690V/800V | 73.5 | 105 | 143 | 176 | |
1140V | 40 | 63 | 105 | 121 | |
Rated short-term withstand current Icw | 400V | 50 | 65 | 100 | 140 |
690V/800V | 35 | 50 | 65 | 80 | |
1140V | 20 | 30 | 50 | 55 | |
Number of operation cycles per hour | 20 | ||||
Electrical life | 400V | 5000 | 5000 | 2500 | 2500 |
690V/800V | 3000 | 3000 | 1500 | 1500 | |
1140V | 1000 | 1000 | 800 | 800 | |
Mechanical life | Maintenance-free | 15000 | 15000 | 8000 | 5000 |
Maintenance | 20000 | 20000 | 10000 | 10000 |
Protection function
Controller model | 2L | M | 3m | 2h | 3H |
Overload long delay protection | ■ | ■ | ■ | ■ | ■ |
Short circuit short delay protection | □ | ■ | ■ | ■ | ■ |
Short circuit instantaneous protection | ■ | ■ | ■ | ■ | ■ |
Ground fault protection | □ | ■ | ■ | ■ | ■ |
Current imbalance protection | - | - | □ | □ | □ |
Functional test | ■ | ■ | ■ | ■ | ■ |
Fault memory | ■ | ■ | ■ | ■ | ■ |
Signal contact output | □ | □ | □ | ■ | ■ |
Hot Memory | ■ | ■ | ■ | ■ | ■ |
Self-diagnosis | ■ | ■ | ■ | ■ | ■ |
MCU working instructions | ■ | - | - | - | - |
Current columnar display | ■ | - | - | - | - |
Current measurement | - | ■ | ■ | ■ | ■ |
MCR and cross-limit trip | □ | □ | □ | □ | □ |
Load monitoring | - | □ | □ | □ | □ |
Fault status indication and numerical display | ■ | ■ | ■ | ■ | ■ |
Voltage measurement | - | □ | □ | ■ | ■ |
Power factor measurement | - | - | □ | ■ | ■ |
Power measurement | - | - | □ | ■ | □ |
Electrical energy measurement | - | - | □ | □ | □ |
Communication function | - | - | - | ■ | ■ |
Contact wear indication | - | - | □ | ■ | ■ |
Regional interlock | - | - | □ | - | □ |
Harmonic measurement | - | - | □ | - | □ |
Voltage protection | - | - | □ | - | □ |
Number of operations records | - | - | □ | ■ | ■ |